Build a spare strategy around the actual 3500 rack configuration.
This case helps document a Bently Nevada 3500 rack before an outage, with emphasis on power-supply redundancy, TDI dependency, monitor modules and field wiring.
Architecture facts to verify
Rack layout
The standard 3500 full-size rack reserves the left-most positions for two power supplies and the rack interface/TDI position. The remaining positions accept monitor and related modules.
Power strategy
A 3500 rack can use one or two 3500/15 power supplies. With two supplies, either supply is capable of powering a full rack, supporting redundancy planning.
TDI dependency
The 3500/22M Transient Data Interface supports rack configuration and communication with System 1. Treat its configuration and rear I/O details as part of the recovery record.
Phase reference
The 3500/25 Enhanced Keyphasor module provides phase-reference information used for speed and vector measurements. Record probe type and channel use.
Rack survey planner
What belongs in the rack record
| Item | Record | Reason |
|---|---|---|
| 3500/05 rack | Rack size, mounting format, slot map | Defines physical architecture. |
| 3500/15 supply | AC/DC type, quantity, input range, spare status | Power redundancy must be understood before service. |
| 3500/22M TDI | Part number, rear I/O, configuration backup | Supports rack configuration and System 1 communication. |
| Monitor modules | Exact model, channel use, I/O module, spare status | Installed function differs by monitor type. |
| 3500/25 Keyphasor | Channel inputs, probe/pickup source | Phase reference can affect diagnostics. |
| Relay modules | Output mapping and voting logic | Trip logic must be documented before replacement. |
Spare tiers
Tier A · Immediate recovery
Modules whose failure can remove rack power, protection coverage or a critical interface with no practical workaround.
Tier B · Short-window recovery
Modules with partial redundancy or temporary operational alternatives, but still significant outage exposure.
Tier C · Planned replacement
Non-critical or duplicated functions where procurement can follow a planned maintenance window.
Official references
Baker Hughes — 3500 Machinery Protection System resources
Baker Hughes — 3500 System Datasheet
Reusable worksheet
Download 3500 rack survey CSVMaintainer
Maintained by PLCProTech Ltd. as an open industrial automation engineering reference.